Fire-resistant hydraulic fluids should be used when there is a possibility that the hydraulic fluid may come into contact with a source of ignition or the surface of high-temperature equipment. This potential fire risk exists in die-making operations, hydraulic operations in continuous casting in steel plants, and pressure operations near presses or heating furnaces.
The high-pressure and high-temperature environment of the electro-hydraulic control (EHC) for regulating the steam supply of steam turbine generators also requires the use of fire-resistant hydraulic fluids to reduce the risk of fire and potential hazards that could result in high costs. Synthetic ester base oils are the most commonly used fluids in electro-hydraulic control of power turbine control systems.
Nevertheless, many other types of flame-resistant fluids can be used in other applications. For all incompatible flame-resistant fluids, special safety measures should be taken when switching from one flame-resistant fluid to another.
What are Fire-resistant Hydraulic Fluids?

Fire-resistant hydraulic fluids are specially formulated lubricants that are more difficult to ignite and will not spread flames from a fire source. Fire resistance should not be confused with fireproofing, as fire-resistant fluids can still ignite and burn under specific conditions.
Fire-resistant hydraulic fluids come in several types and are typically classified as follows:
- Oil-in-Water Emulsions
- Water-in-Polymer Solutions
- Waterless Synthetic Fluids
More specifically, the International Organization for Standardization (ISO) further classifies these fluids as follows:
HFAE—Water-in-oil emulsion, typically containing over 80% water
HFAS—Synthetic aqueous fluid, typically containing over 80% water
HFB—Oil-in-water emulsion, typically containing over 40% water
HFC—Water-polymer solution, typically containing over 35% water (also known as ethylene glycol solution, polyalkylene glycol solution, or water-glycol)
HFDR—Synthetic anhydrous fluid composed of phosphates
HFDU—Synthetic anhydrous fluid excluding phosphates. Examples include polyol esters and polyalkylene glycols
Replace or Convert to Fire-Resistant Fluid

We can provide detailed conversion procedures covering all possible conversion scenarios. The International Organization for Standardization (ISO) specifically addresses four conversions:
- Conversion from a mineral oil to a water-based fluid (classified as HFAE, HFB, or HFC)
- Conversion from a mineral oil to a synthetic anhydrous fluid (classified as HFD)
- Conversion from a water-based fluid (classified as HFAE, HFB, or HFC) to a synthetic water-free fluid (classified as HFD)
- Conversion from a synthetic water-free fluid (classified as HFD) to a water-based fluid (classified as HFAE, HFB, or HFC)
The key inspection points for any conversion or replacement are as follows:
- Compatibility of each replaceable component in the circuit (seals, packing, hoses, and coatings) with the fire-resistant fluid to be introduced into the circuit
- Drainage and flushing (pipes, valves, tanks, coarse filters, filters and filter cartridges, pumps, etc.)
- Flush
- Refill and inspection, including specific system and oil monitoring (conversion to HFC fluids may cause filter blockage due to their contaminant-removal properties, dislodging previously formed deposits)
Conversion from a Mineral Oil to a Water-Based Fluid (HFAE, HFAS, HFB, or HFC) or a Synthetic Water-Free Fluid (HFD)
Special attention should be paid to when fluids are compatible, as even small amounts of residual mineral oil can weaken the fire resistance and stability of the replaced water-based fluid (HFAE, HFB, or HFC). Similarly, there is at least partial miscibility between mineral oil and synthetic anhydrous fluids (classified as HFD). Therefore, while minimal residual mineral oil does not alter the properties of an HFD fluid, it may diminish its fire-resistant characteristics.
Switching from One Fire-Resistant Hydraulic Fluid to Another

When a system is converted from one type of fire-resistant hydraulic fluid to another type of fire-resistant hydraulic fluid with a different classification, these two types of fire-resistant fluids must not be mixed.
For example, mixing any water-based fluid (HFA, HFB, or HFC) with a synthetic anhydrous fluid (HFDR or HFDU) will result in a two-phase system (water phase and oil phase separation), potentially causing pump failure.
Additionally, it is recommended not to mix fluids of the same category but from different suppliers unless compatibility has been confirmed. Brand names may be confusing, so consult the fluid supplier to confirm the precise type of fluid used in the equipment (classified as HFA, HFB, HFC, or HFD according to ISO standards). Consult both the fluid and system manufacturers to understand compatibility with various seals, metals, and coatings, as compatibility can vary significantly if the chemical compositions of these materials differ.
Fire-Resistant Classification and Related Operating Temperature Summary Table
| Base Type | ISO Classification | Subcategory | Ingredients | Moisture | Typical Temperature Range (Per ISO) | Note |
| Water-based | HFA | HFAE | Water-in-oil Emulsion | >80% (typically 95%) | +5 ~ +50°C | Storage temperature > 0°C |
| Water-based | HFA | HFAS | Synthetic Water-Based Fluid | 80% (typically 95%) | +5 ~ +50°C | Storage temperature > 0°C |
| Water-based | HFB | —— | Oil-in-water (emulsion conversion) | >40% | +5 ~ +50°C | Storage temperature > 0°C |
| Water-based | HFC | —— | Aqueous Polymer Solution | >35% | -20 ~ +50°C | —— |
| Non-water-based | HFD | HFDR | Phosphate Ester | None | -20 ~ +70°C | In certain applications, the maximum temperature may reach 150°C. However, at this temperature, the fluid may deteriorate rapidly and should be inspected frequently (the upper temperature limit permits only short-term operation). For high-temperature circuits exceeding +100°C, seals, packing, hoses, and other components must utilize specialized materials. If in doubt, consult the equipment manufacturer and/or fluid supplier for clarification. |
| Non-water-based | HFD | HFDU | Synthetic anhydrous fluids (polyalkylene glycol/polyol esters), excluding phosphate esters | None | -20 ~ +70°C | In certain applications, the maximum temperature may reach 150°C. However, at this temperature, the fluid may deteriorate rapidly and should be inspected frequently (the upper temperature limit permits only short-term operation). For high-temperature circuits exceeding +100°C, seals, packing, hoses, and other components must utilize specialized materials. If in doubt, consult the equipment manufacturer and/or fluid supplier for clarification. |
Conclusion
In equipment operating under fire risks or high temperatures, using fire-resistant hydraulic fluids is essential for ensuring system safety and stability. Selecting the appropriate fluid and executing the conversion correctly can effectively reduce failures and potential hazards.
If you are planning a fluid change, evaluating compatibility, or unsure which type of fire-resistant hydraulic fluid to choose, feel free to contact Evisco anytime. Evisco provides tailored fire-resistant hydraulic oil solutions based on your equipment type, operating temperature, seal materials, and current oil category. We deliver detailed conversion steps, cleaning protocols, and post-conversion monitoring recommendations.
Like steel mills, die-casting lines, turbine EHC systems, or other high-temperature hydraulic equipment, Evisco offers expert assessment, technical support, and ongoing service.